VRV S

To suit the variety of rooms found in small offices and shops, the VRVIII-S system offers wide range of indoor and outdoor units.
VRVIII-S indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
Product Category
- VRV Air Conditioner VRV S
Model
RX(Y)MQ4, RX(Y)MQ5, RX(Y)MQ6, RX(Y)MQ8, RX(Y)MQ10, RX(Y)MQ12
Specification
Outdoor Units
MODEL | RX(Y)MQ4 | RX(Y)MQ5 | RX(Y)MQ6 | RX(Y)MQ8 | RX(Y)MQ10 | RX(Y)MQ12 | ||
Power supply | 1-phase, 230V, 50Hz | 3-phase, 380-415V, 50Hz | ||||||
Cooling capacity | Kcal/h | 9,600 | 12,000 | 13,000 | 19,300 | 24,100 | 28,800 | |
Btu/h | 38,200 | 47,800 | 52,900 | 76,400 | 95,500 | 1,14,000 | ||
Kw | 11.2 | 14.0 | 15.5 | 22.4 | 28.0 | 33.5 | ||
Capacity Control | % | 24-100 | 24-100 | 24-100 | 20-100 | 16-100 | 16-100 | |
Casing Colour | Ivory white | |||||||
Compressor | Type | Hermetically Sealed Scroll Type | ||||||
No. of compressor | 1 | 1 | 1 | 1 | 1 | 1 | ||
Airflow rate | m3/min | 106 | 106 | 106 | 140 | 182 | 182 | |
Dimensions (H×W×D) | mm | 1345x900x320 | 1345x900x320 | 1345x900x320 | 1430x940x320 | 1615x940x460 | 1615x940x460 | |
Machine weight | kg | 125 | 125 | 125 | 131 | 164 | 170 | |
Sound level | dB(A) | 50 | 51 | 53 | 57 | 59 | 60 | |
Operation range |
Cooling | °CDB | -5 ~ 46 | |||||
Heating | °CDB | -20 ~ 15.5 | ||||||
Refrigerant | Type | R410A | ||||||
Charge | kg | 4.0 | 4.0 | 4.0 | 5.8 | 7.0 | 8.0 | |
Piping connections |
Liquid | mm | ø9.5 (Flare) | ø9.5 (Flare) | ø9.5 (Flare) | ø9.5 (Brazing) | ø9.5 (Brazing) | ø12.7 (Brazing) |
Gas | mm | ø15.9 (Flare) | ø15.9 (Flare) | ø19.1 (Brazing) | ø19.1 (Brazing) | ø22.2 (Brazing) | ø25.4 (Brazing) |
Note :
Specifications are based on the following conditions:
- Cooling: Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
- Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5m, Level difference: 0m.
- Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
- Refrigerant charge is required.