Daikin's new range of rooftop packaged unit has been developed specifically to suit commercial application and are designed to be easy to install, requiring only ducting (and associated fittings), power/control wiring and drain piping. Designed for high ambient application. Continuous operation at an outdoor ambient temp. up to 52℃.

Product Category
Model
UATQ60/90/120/150/180/210/240/300C

Specification

Rooftop Series (Cooling Only)

r410a
Model 5.2 TR 7.8 TR 10.4 TR 12.9 TR 15.8 18.3 20.7 26.0
UATQ60C UATQ90C UATQ1 20C UATQ150C UATQ1 80C UATQ240C UATQ240C UATQ300C
Rated Capacity Btu 62,500 93,400 1,24,500 1,54,400 1,89,000 2,20,000 2,48,600 3,12,200
  kW 18.32 27.37 36.49 45.25 55.39 64.48 72.86 91.5
Total Power Input kW 4.52 7.20 9.45 12.00 14.72 16.90 19.29 24.52
Total Running Current A 8.20 13.50 17.00 24.10 27.20 33.90 38.70 46.00
COP W/W 4.05 3.80 3.86 3.77 3.76 3.82 3.78 3.73
Power Source V/Ph/Hz 380-415V/3/50 380-415V/3/50 380-415V/3/50 380-415V/3/50 380-415V/3/50 380-415V/3/50 380-415V/3/50 380-415V/3/50
Control Operation   Wired Control Wired Control Wired Control Wired Control Wired Control Wired Control Wired Control Wired Control
Air Flow cfm 2000 2800 4400 5000 7000 7600 8000 9000
External Static Pressure
(Factory Setting)"
Pa 50-500(100) 50-500(100) 50-500(100) 50-500(150) 50-500(150) 50-500(200) 50-500(200) 50-500(250)
Fan Drive   Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven
Air Quality(Filter) Type Saranet Saranet Saranet Saranet Saranet Saranet Saranet Saranet
Qty 1 1 2 2 2 2 2 2
Unit Dimension (HxWxD) mm 1150 x 1280 x 1520 1350 x 1280 x 1520 1390 x 1965 x 1630 1390 x 1965 x 1630 1690 x 1965 x 1905 1650 x 2410 x 2030 1650 x 2410 x 2030 1950 x 2410 x 2030
Packing Dimension
(HxWxD)
mm 1270 x 1320 x 1710 1410 x 1320 x 1710 1440 x 2020 x 1840 1440 x 2020 x 1840 1730 x 2120 x 2020 1740 x 2570 x 2290 1740 x 2570 x 2290 2040 x 2570 x 2290
Unit Weight kg 350 380 590 650 840 930 940 1090
Gross Weight kg 370 400 620 680 870 970 980 1130
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Qty 1 1 2 2 2 2 2 2
Refrigerant (PreCharged) Kg 9.5 11.5 5.2 + 5.2 8.5 + 8.5 8.5 + 8.5 12.0 + 12.0 10.8 + 10.8 14.0 + 14.0
Operating Range CDB up to 52°C up to 52°C up to 52°C up to 52°C up to 52°C up to 52°C up to 52°C up to 52°C

Note :

  • Gross Cooling Capacity Based on 27°C DB / 19°C WB Indoor and 35°C DB outdoor
  • All Units are being tested and Comply to ISO 5151 (Non-Ducted Unit) or ISO 13253 (Ducted Unit)