Enquire Now

Air Cooled Rooftop UATQ-C, R410A Series (Cooling only)

Daikin's new range of rooftop packaged unit has been developed specifically to suit commercial application and are designed to be easy to install, requiring only ducting (and associated fittings), power/control wiring and drain piping. Designed for high ambient application. Continuous operation at an outdoor ambient temp. up to 52℃.

Product category:

Model: 
UATQ60/90/120/150/180/210/240/300C

Specification

Rooftop Series (Cooling Only)

r410a
Model5.2 TR7.8 TR10.4 TR12.9 TR15.818.320.726.0
UATQ60CUATQ90CUATQ1 20CUATQ150CUATQ1 80CUATQ240CUATQ240CUATQ300C
Rated CapacityBtu62,50093,4001,24,5001,54,4001,89,0002,20,0002,48,6003,12,200
 kW18.3227.3736.4945.2555.3964.4872.8691.5
Total Power InputkW4.527.209.4512.0014.7216.9019.2924.52
Total Running CurrentA8.2013.5017.0024.1027.2033.9038.7046.00
COPW/W4.053.803.863.773.763.823.783.73
Power SourceV/Ph/Hz380-415V/3/50380-415V/3/50380-415V/3/50380-415V/3/50380-415V/3/50380-415V/3/50380-415V/3/50380-415V/3/50
Control Operation Wired ControlWired ControlWired ControlWired ControlWired ControlWired ControlWired ControlWired Control
Air Flowcfm20002800440050007000760080009000
External Static Pressure
(Factory Setting)"
Pa50-500(100)50-500(100)50-500(100)50-500(150)50-500(150)50-500(200)50-500(200)50-500(250)
Fan Drive Belt DrivenBelt DrivenBelt DrivenBelt DrivenBelt DrivenBelt DrivenBelt DrivenBelt Driven
Air Quality(Filter)TypeSaranetSaranetSaranetSaranetSaranetSaranetSaranetSaranet
Qty11222222
Unit Dimension (HxWxD)mm1150 x 1280 x 15201350 x 1280 x 15201390 x 1965 x 16301390 x 1965 x 16301690 x 1965 x 19051650 x 2410 x 20301650 x 2410 x 20301950 x 2410 x 2030
Packing Dimension
(HxWxD)
mm1270 x 1320 x 17101410 x 1320 x 17101440 x 2020 x 18401440 x 2020 x 18401730 x 2120 x 20201740 x 2570 x 22901740 x 2570 x 22902040 x 2570 x 2290
Unit Weightkg3503805906508409309401090
Gross Weightkg3704006206808709709801130
CompressorTypeScrollScrollScrollScrollScrollScrollScrollScroll
Qty11222222
Refrigerant (PreCharged)Kg9.511.55.2 + 5.28.5 + 8.58.5 + 8.512.0 + 12.010.8 + 10.814.0 + 14.0
Operating RangeCDBup to 52°Cup to 52°Cup to 52°Cup to 52°Cup to 52°Cup to 52°Cup to 52°Cup to 52°C

Note :

  • Gross Cooling Capacity Based on 27°C DB / 19°C WB Indoor and 35°C DB outdoor
  • All Units are being tested and Comply to ISO 5151 (Non-Ducted Unit) or ISO 13253 (Ducted Unit)
  • All specifications are Subjected to Change by the manufacturer without prior notice

AS A PART OF CONTINOUS DEVELOPMENT AND UPGRADATION THE PRODUCT IMAGE/ACCESSORY/FEATURE/SPECIFICATION MAY BE DIFFERENT FROM ACTUAL PRODUCT AT THE TIME OF PURCHASE.

Customer Support Information: Give A Missed Call: @ 9210188999, Call Our Customer Contact Centre: 011-40319300or Write To Us at: customerservice@daikinindia.com