Enquire Now

FVRN & FVQN Series

Cooling Only & Heat Pump

Never compromise on style over functionality with our latest range of floor standing air conditioners. They are immensely powerful and designed to complete your existing décor. Due to their ease in installation, they are a perfect choice for offices, commercial shops, restaurants, and showrooms.

Product category:

Available in (kW):

Specification

Floor Standing (Cooling Only)

r-410-a
Model nameIndoorFVRN71AXV16FVRN100AXV16FVRN125AXV16FVRN140AXV16
OutdoorRR71CGXY1A6RR100DGXY16RR125DGXY16RR140DGXY16
Nominal Cooling CapacityTonnage2.43.33.84.6
Btu/hr28500400004500055000
kw8.3511.7213.1916.12
Nominal Total Input Power (Cooling)w2750405047505490
Nominal Running Current (Cooling)A137.078.299.35
Power SourceV/Ph/Hz380-415 / 3 / 50
Refrigerant Control (Expansion Device)OUTDOOR CAPILLARY TUBE
Refrigerant TypeR410A
Indoor unit
Air FlowHighCFM1035103510351170
Medium9459459351085
Low845845835985
Quiet----
Sound Pressure LevelHighdBA49495054
Medium47474853
Low44444651
Quiet----
Unit Dimension [Panel]Heightmm1850185018501850
Widthmm600600600600
Depthmm350350350350
Unit Weight [Panel]kg45454851
Outdoor unit
Unit DimensionmmHEIGHT753852852852
mmWIDTH855103010301030
mmDEPTH328400400400
Unit Weightkg569598105
Pipe ConnectionType FLARE VALVE
Liquidmm9.52
Gasmm15.8819.05
Max Piping Lengthm45
Max Piping Elevationm25

Note :

  • Rated cooling capacities are based on the following conditions: Indoor temp., 27˚CDB, 19˚CWB; outdoor temp. 35˚CDB.
  • All unit are being tested and comply to ISO 5151 (Non-ducted unit)

Floor Standing (Heat Pump)

r-410-a
Model Name 100125140
Indoor unit FVQN100AXV1FVQN125AXV1FVQN140AXV1
Outdoor unit RQ100DGXY1RQ125DGXY1RQ140DGXY1
Rated Cooling CapacityBtu/h400004500055000
kW11.7213.1916.12
Rated EERW/W 2.822.94
Btu/h420004600054500
Rated Heating CapacitykW12.3113.4816
Rated COPW/W3.143.023.01
Indoor unit
Power SupplyV/Ph/Hz220-240/1/50
Air Flowcfm1035/945/8451170/1085/985
Sound Pressure LeveldBA49/47/4450/48/4654/53/51
Heightmm1850
Widthmm600
Depthmm350
Net Weightkg454851
Outdoor unit
Power SupplyV/Ph/Hz380-415/3/50
Sound Pressure LeveldBA586065
Heightmm 852
Widthmm 1030
Depthmm 400
Net Weightkg9598105
Pipe Connection - Liquidmm9.52
Pipe Connection - Gasmm15.8819.05
Max. Allowable Lengthm4540
Max. Allowable Elevationm2520

Note :

  • Rated cooling capacities are based on the following conditions: Indoor temp., 27˚CDB, 19˚CWB; outdoor temp. 35˚CDB.
  • Rated heating capacities are based on the following conditions: Indoor temp., 20˚CDB; outdoor temp., 7˚CDB, 6˚CWB.
  • All unit are being tested and comply to ISO 5151 (Non-ducted unit)

AS A PART OF CONTINOUS DEVELOPMENT AND UPGRADATION THE PRODUCT IMAGE/ACCESSORY/FEATURE/SPECIFICATION MAY BE DIFFERENT FROM ACTUAL PRODUCT AT THE TIME OF PURCHASE.

Customer Support Information: Give A Missed Call: @ 9210188999, Call Our Customer Contact Centre: 011-40319300or Write To Us at: customerservice@daikinindia.com